SmartGen HAT560NB

SmartGen HAT560NB ATS Controller User Manual

1. Hyrje

The SmartGen HAT560NB ATS Controller is an intelligent dual-supply module designed for Automatic Transfer Systems (ATS). It integrates digital, intelligent, and networked functionalities to provide precise voltage measurement and control for various power supply configurations. This controller is suitable for specialized ATS, Contactor ATS, and Air Break ATS applications, offering a compact structure, advanced circuitry, and high reliability.

It is engineered to reduce operational errors through automatic measurement and control, making it an ideal solution for managing power transfer between different sources like mains and generators.

SmartGen HAT560NB ATS Controller front view with LCD display and control buttons

Figura 1: Përpara view of the SmartGen HAT560NB ATS Controller, showing the LCD display and operational buttons.

2. Features and Characteristics

The HAT560NB controller incorporates a powerful microprocessor for accurate monitoring and control. Key features include:

  • System type configuration: Mains (1#) & Generator (2#), Generator (1#) & Mains (2#), Mains (1#) & Mains (2#), Generator (1#) & Generator (2#).
  • 132x64 LCD with backlight, offering optional Chinese and English display with push-button operation.
  • Measurement and display of 2-way 3-phase voltage dhe frekuencës.
  • Mbrojtja kundër mbi/nën voltage, loss of phase, reverse phase sequence, and over/under frequency.
  • Automatic and Manual operating modes. Manual mode allows forced switch closure or opening.
  • All parameters are configurable on-site, secured by two different passwords for authorized access.
  • Genset commissioning can be set to On-load or Off-load mode.
  • Automatic re-closing function for the ATS Controller.
  • Configurable closing output signal as either on intervals or continuous output.
  • Applicable for ATS with one neutral position, two neutral positions, and non-position types.
  • Monitors 1-3 phase AC mains voltages.
  • Manages changeover of both generator and mains contactors.
  • Sends remote start commands to the generating set.
  • Compatible with various contactors and changeover switch types.

3. Konfigurimi dhe instalimi

Proper installation is crucial for the safe and reliable operation of the HAT560NB controller. Ensure all power is disconnected before beginning installation. Refer to the wiring diagrams and terminal descriptions for correct connections.

3.1 Diagramet e instalimeve elektrike

The HAT560NB controller supports various wiring configurations depending on the ATS type. Below are typical wiring diagrams for different setups. Always consult a qualified electrician for installation.

Multiple wiring diagrams for ATS controllers including ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG types

Figure 2: Comprehensive wiring diagrams illustrating connections for ATYS3S, SGQ-N/T, SGQ-M, and VITZRO/PHETENG ATS controller types. These diagrams show connections for 1# and 2# power supplies, load, and remote start signals.

Detailed wiring diagrams for SGQ-N/T, SGQ-M, and Contactor ATS configurations

Figure 3: Additional wiring diagrams focusing on SGQ-N/T, SGQ-M, and Contactor ATS configurations, detailing input and output connections for the controller.

3.2 Lidhja e terminaleve

The controller features clearly labeled terminals for power input, auxiliary outputs, and control signals. Ensure each wire is securely connected to its designated terminal.

E pasme view of the HAT560NB controller showing labeled connecting terminals for inputs and outputs

Figura 4: E pasme view of the HAT560NB controller, displaying the layout and labeling of all connecting terminals, including power inputs, auxiliary outputs, and communication ports.

4. Udhëzimet e funksionimit

The HAT560NB controller offers both automatic and manual operation modes, accessible via its front panel buttons and LCD display.

4.1 Power On and Initial Display

Upon powering on, the LCD will display system information, including voltage and frequency readings for both power sources. The backlight ensures visibility in various lighting conditions.

4.2 Zgjedhja e modalitetit

  • Modaliteti automatik: The controller automatically monitors the power sources and initiates transfer based on pre-set parameters and detected abnormalities (e.g., over/under voltage, frequency deviations, phase loss).
  • Modaliteti manual: Allows the user to manually control the opening or closing of the transfer switches. This mode is typically used for testing or specific operational requirements.

4.3 Vendosja e parametrave

All operational parameters can be configured directly on the unit using the push-buttons and LCD interface. Access to parameter settings is protected by a two-level password system to prevent unauthorized changes. Refer to the detailed programming guide (not included in this manual) for specific parameter definitions and adjustment procedures.

5. Mirëmbajtja

Regular maintenance ensures the longevity and reliable performance of your HAT560NB ATS Controller.

  • Pastrimi: Keep the controller's exterior clean and free from dust and debris. Use a soft, dry cloth. Avoid abrasive cleaners or solvents.
  • Kontrollet e lidhjes: Periodically inspect all wiring connections to ensure they are secure and free from corrosion. Loose connections can lead to intermittent operation or system failures.
  • Kushtet e mjedisit: Sigurohuni që mjedisi i funksionimit të mbetet brenda diapazonit të specifikuar të temperaturës dhe lagështisë për të parandaluar dëmtimin e komponentëve të brendshëm.

Për çdo mirëmbajtje ose riparim të brendshëm, kontaktoni personelin e kualifikuar të shërbimit.

6. Troubleshooting

This section provides guidance on common issues you might encounter with the HAT560NB controller.

ProblemShkaku i mundshëmZgjidhje
Kontrolluesi nuk ndizetNo DC power supply; Incorrect wiringCheck DC 8.0V-35.0V power supply connections; Verify wiring according to diagrams.
ATS nuk transferohet automatikishtAutomatic mode not selected; Fault detected on active power source (e.g., over/under voltage, frequency); Incorrect parametersEnsure controller is in Automatic mode; Check power source status; Verify parameter settings.
Display shows error for voltage/frekuencaActual power source issue; Sensor/input wiring problemKontrolloni vëllimin aktualtage and frequency of the power source; Inspect AC voltage instalime elektrike hyrëse.
Butonat nuk reagojnëTemporary software glitch; Hardware issueRestart the controller by cycling power; If issue persists, contact support.

7. Specifikimet

The following table details the technical specifications for the SmartGen HAT560NB ATS Controller.

Table of specifications for SmartGen HAT560N series ATS Controller

Figure 5: Detailed specifications table for the HAT560N series ATS Controller, including operating voltage, power consumption, AC voltage input ranges, rated frequency, relay outputs, communication, dimensions, and environmental conditions.

ArtikulliSpecifikimi
Vëllimi operativtageDC 8.0V-35.0V (continuous power supply)
AC Voltage InputAC170V-270V (during AC power L1N1/L2N2 supply)
Konsumi i energjisë<3W (modaliteti i gatishmërisë: <2W)
Frekuenca e vlerësuar50/60 Hz
Mbyll daljen e stafetës16A AC250V (Volts free output)
Dalja e stafetës ndihmëse 17A AC250V (Volts free output)
Dalja e stafetës ndihmëse 27A AC250V (Volts free output)
Dalja e stafetës ndihmëse 316A AC250V (Volts free output)
Dalja e stafetës ndihmëse 416A AC250V (Volts free output)
Hyrja dixhitaleGND connect is active
KomunikimiNdërfaqja LINK, Protokolli MODBUS
Dimensionet e kasës139 mm x 120 mm x 48 mm (5.47 x 4.72 x 1.89 inç)
Prerja e panelit130 mm x 111 mm
Kushtet e PunësTemperature: (-25~+70)°C, Humidity: (20~93)%RH
Gjendja e ruajtjesTemperatura: (-25~+70)°C
Niveli i mbrojtjesGuarnicioni IP55
Forca e izolimitAplikoni AC2.2kV voltage ndërmjet vëllimit të lartëtage terminalit dhe vëllimit të ulëttage terminali; Rryma e rrjedhjes nuk është më shumë se 3 mA brenda 1 min.
Pesha0.62 kg (1.63 paund)

Dokumente të Ngjashme - HAT560NB

Paraview SmartGen HAT560N Series ATS Controller User Manual - Dual Power Transfer Automation
Comprehensive user manual for the SmartGen HAT560N and HAT560NB ATS Controllers. Covers features, specifications, operation, configuration, wiring diagrams, and troubleshooting for dual power transfer systems.
Paraview Manuali i Përdoruesit të Kontrolluesit HAT72 ATS
Manuali i përdoruesit për Kontrolluesin e Ndërprerësit Automatik të Transferimit (ATS) Smartgen HAT72, i cili detajon karakteristikat e tij, parametrat teknikë, funksionimin, lidhjet e terminalit dhe instalimet elektrike tipike për ndërrimin e energjisë nga rrjeti elektrik dhe gjeneratori. I projektuar për transferim automatik të besueshëm të energjisë.
Paraview Manuali i përdorimit të kontrolluesit SmartGen HAT520N ATS
User manual for the SmartGen HAT520N Dual Power ATS Controller, detailing its performance, specifications, panel operations, parameter configuration, installation, and troubleshooting.
Paraview Manuali i përdorimit të kontrolluesit SmartGen HAT530N ATS
This user manual provides comprehensive instructions and specifications for the SmartGen HAT530N ATS Controller. Learn about its features, operation, parameter settings, wiring diagrams, and troubleshooting.
Paraview Manuali i Përdoruesit të Kontrolluesit ATS me Bypass të Dyfishtë të Energjisë SmartGen HAT880 Series
Ky manual përdorimi ofron udhëzime të hollësishme operative dhe teknike për Kontrolluesin ATS me Bypass të Dyfishtë të Energjisë SmartGen HAT880 Series (HAT880/HAT880S), duke mbuluar karakteristikat, specifikimet, funksionimin, instalimin dhe zgjidhjen e problemeve për një menaxhim të besueshëm të energjisë së dyfishtë.
Paraview Manuali i Përdoruesit dhe Specifikimet e Ndërprerësit Automatik të Transferimit (ATS) SmartGen HAT520N
Manual gjithëpërfshirës përdorimi dhe specifikime teknike për kontrolluesin e Ndërprerësit Automatik të Transferimit (ATS) SmartGen HAT520N, që mbulon funksionimin, sigurinë, instalimin dhe zgjidhjen e problemeve për konfigurime të ndryshme të furnizimit me energji.