1. Hyrje
This manual provides detailed instructions for the installation, operation, maintenance, and troubleshooting of the HOCHIKI HCA-4D/120V 6.5 Amp 4 Zone Conventional Fire Alarm Control Panel (FACP) with Digital Alarm Communicator Transmitter (DACT). Please read this manual thoroughly before attempting to install or operate the unit. Retain this manual for future reference.
2. Informacion mbi sigurinë
PARALAJMËRIM: Rrezik goditjeje elektrike. Shkëputni energjinë përpara se të kryeni shërbimin.
Always follow local and national electrical codes and standards during installation. Only qualified personnel should install and service this equipment. Ensure proper grounding. Do not expose the unit to moisture or extreme temperatures. Failure to comply with these safety instructions may result in injury, damage to the equipment, or improper operation of the fire alarm system.
3. Produkti i Mbaruarview
The HOCHIKI HCA-4D/120V is a conventional fire alarm control panel designed for small to medium-sized applications. It features four initiating device circuits (zones) and a built-in Digital Alarm Communicator Transmitter (DACT) for remote monitoring. The panel operates on a 120V AC power supply and provides 6.5 Amps of power for system operation.

Figura 1: Përpara view of the HOCHIKI HCA-4D/120V Fire Alarm Control Panel. This image shows the main enclosure with indicator lights and control buttons.
Karakteristikat kryesore:
- 4 Conventional Initiating Device Circuits (Zones)
- Built-in Digital Alarm Communicator Transmitter (DACT)
- 6.5 Amp Furnizimi me energji elektrike
- Funksionim 120V AC
- Alarm, Trouble, and Supervisory Indicators
- Silence, Reset, and Acknowledge Controls
4. Konfigurimi dhe instalimi
4.1 Shpaketimi dhe inspektimi
- Carefully unpack the FACP and all components.
- Inspektoni për çdo dëmtim gjatë transportit. Raportoni menjëherë çdo dëmtim te transportuesi.
- Verify all components listed in the packing slip are present.
4.2 Montimi i panelit
- Select a clean, dry, and secure location for mounting, away from potential sources of interference or damage.
- Ensure adequate space for ventilation and access for wiring and servicing.
- Mount the panel securely to a wall using appropriate fasteners.
4.3 Lidhjet e instalimeve elektrike
All wiring must comply with NFPA 70 (National Electrical Code) and NFPA 72 (National Fire Alarm and Signaling Code), as well as local codes.
- Lidhja e energjisë: Connect the 120V AC power supply to the designated terminals. Ensure the power source is protected by a dedicated circuit breaker.
- Lidhja e baterisë: Connect the standby batteries to the battery terminals, observing correct polarity.
- Initiating Device Circuits (Zones): Connect fire alarm initiating devices (smoke detectors, heat detectors, manual pull stations) to the respective zone terminals. Each zone requires an End-of-Line Resistor (EOLR).
- Notification Appliance Circuits (NACs): Connect audible and visual notification appliances (horns, strobes) to the NAC terminals. Observe polarity and ensure EOLRs are installed.
- DACT Connection: Connect the DACT to a dedicated telephone line for communication with the central monitoring station.
- Auxiliary Relays: If applicable, connect auxiliary devices to the programmable relay outputs.
4.4 Ndezja fillestare
- Para se të lidhni energjinë elektrike, kontrolloni dy herë të gjitha lidhjet e instalimeve elektrike për saktësi dhe siguri.
- Apply AC power to the panel. The AC POWER indicator should illuminate.
- Connect the standby batteries.
- The panel will perform a self-test. Any troubles will be indicated.
5. Udhëzimet e funksionimit
5.1 Operacioni normal
In normal operation, the green AC POWER indicator is illuminated. All other indicators should be off, and the system should be free of trouble conditions.
5.2 Kushtet e alarmit
When an initiating device activates (e.g., smoke detector detects smoke), the following occurs:
- The ALARM indicator illuminates.
- The specific ZONE ALARM indicator illuminates.
- Notification appliances (horns/strobes) activate.
- The DACT transmits an alarm signal to the central monitoring station.
5.3 Acknowledging an Alarm
Shtypni PRANOJ button to silence the panel's internal buzzer and acknowledge the alarm. Notification appliances will continue to operate until silenced.
5.4 Silencing Notification Appliances
Shtypni HESHTJE button to turn off the horns and strobes. The ALARM indicator will remain illuminated until the system is reset.
5.5 Rivendosja e sistemit
After the alarm condition has been cleared and notification appliances are silenced, press the RISET button. The panel will attempt to reset all initiating devices and return to normal operation. If the alarm condition persists, the system will re-alarm.
5.6 Trouble Conditions
A trouble condition indicates a fault in the system (e.g., open circuit, short circuit, ground fault, low battery). When a trouble occurs:
- The TROUBLE indicator illuminates.
- The specific ZONE TROUBLE or SYSTEM TROUBLE indicator illuminates.
- The panel's internal buzzer activates.
Shtypni PRANOJ button to silence the internal buzzer. Investigate and resolve the cause of the trouble. Once the trouble is cleared, the TROUBLE indicator will extinguish automatically.
6. Mirëmbajtja
Regular maintenance is crucial for the reliable operation of your fire alarm system. Refer to NFPA 72 for detailed inspection, testing, and maintenance requirements.
6.1 Kontrollet Ditore/Javore
- Verify the AC POWER indicator is illuminated.
- Check for any illuminated trouble indicators.
6.2 Monthly Checks
- Test all initiating devices (smoke detectors, heat detectors, pull stations) for proper operation.
- Test all notification appliances (horns, strobes).
- Test the DACT communication to the central monitoring station.
6.3 Kontrollet vjetore
- Perform a comprehensive system test, including all devices and functions.
- Inspektoni të gjitha instalimet elektrike për dëmtime ose lidhje të lirshme.
- Test standby batteries under load to ensure they can provide adequate power during an AC power failure. Replace batteries every 3-5 years or as recommended by the manufacturer.
- Clean the interior of the panel and detectors as necessary.
7. Troubleshooting
| Problem | Shkaku i mundshëm | Zgjidhje |
|---|---|---|
| Panel in Trouble Condition | Open circuit on a zone or NAC, short circuit, ground fault, low battery, AC power failure. | Check specific trouble indicator. Inspect wiring for breaks or shorts. Test battery voltage. Restore AC power. Consult a qualified technician. |
| No AC Power Indicator | No AC power, blown fuse, faulty transformer. | Check circuit breaker. Replace fuse. Contact a qualified technician. |
| DACT Not Communicating | Telephone line issue, DACT programming error, central station issue. | Verify telephone line is active. Check DACT programming. Contact central monitoring station. |
| Alarmet e rreme | Detektor tymi i ndotur, faktorë mjedisorë (pluhur, avull), pajisje e dëmtuar. | Clean smoke detectors. Identify and eliminate environmental factors. Replace faulty devices. |
8. Specifikimet
- Modeli: HCA-4D/120V
- Marka: HOCHIKI
- Volumi i hyrjestage: 120 V AC
- Vlerësimi aktual: 6.5 Amps
- Numri i Zonave: 4 Conventional Zones
- Komunikuesi: Built-in Digital Alarm Communicator Transmitter (DACT)
- UPC: 742779307880
- Data e parë e disponueshme: 4 mars 2022
9. Informacioni i garancisë
HOCHIKI products are manufactured under strict quality control standards. This product is covered by a limited warranty against defects in materials and workmanship. The specific terms and duration of the warranty may vary. Please refer to the warranty card included with your product or contact HOCHIKI customer support for detailed warranty information. Keep your proof of purchase for warranty claims.
10. Mbështetje Teknike
For technical assistance, troubleshooting beyond this manual, or service inquiries, please contact your authorized HOCHIKI distributor or HOCHIKI customer support.
HOCHIKI Customer Support:
Webfaqe: www.hochiki.com
Telefoni: Referojuni webfaqe për numrat e kontaktit rajonal.
When contacting support, please have your product model number (HCA-4D/120V) and serial number ready.